Satisfaction guaranteed. Call us anytime: 1-877-880-TILE (8453).
Cart: 0 items, $0.00

Your shopping cart is empty.

Checkout

Underfloor heating Specifications and installation procedure

January 25, 2010

By SunTouch® A division of Watts Water Technologies, Inc.

The perfect solution for nearly every type of floor covering.

UnderFloor heat, GroupStat, LoudMouth, Heated floor mat, heat mat, radiant floor heat mat, radiant floor heating supply, radiant floor heating mat, radiant floor mat, flooring heating System, tile heating

Introducing

UnderFloor mats are the perfect solution for nearly every type of floor covering.

These special mats warm existing floors without having to replace the floor coverings.

If you have access under a floor, simply staple UnderFloor mats between the joists.

SunTouch UnderFloor is a safe and efficient electric floor-warming product for interior applications. It is intended only for installation under a wood subfloor in residential and light commercial installations. It is not designed for other purposes such as roof snow melting.

Any use or installation of this product other than what is stated in this installation manual will void the Limited Warranty.

SunTouch UnderFloor is designed to deliver approximately 10 watts/sq. ft. of floor area. The temperature of the warm floor is dependent on how well the floor is insulated, as well as the insulating value of the flooring materials. If the joist space is sealed against air leakage, exterior rim joists are insulated, and the underneath side of the floor is insulated, most floors can be heated up to 15°F warmer than they would otherwise be.

Due to the insulating value of carpet, carpeted floors may not achieve the same temperature rise. The floor may or may not achieve this temperature rise, and no representations are made regarding the performance of any system.

For best results, install, un-faced fiber glass R-1 9 or R-1 3 (or equivalent) below the mat.

Do not insulate below the mat with more than R-1 9, and no more than R-1 1 total on top of the subfloor, including all floor coverings, rugs and other items placed on top. SunTouch UnderFloor can be used to heat a room, as well as warm the floor, provided the heat loss of the room falls within the mat’s capabilities. A designer must determine if the output from the SunTouch UnderFloor is enough to match the heat loss of the structure.

The SunTouch UnderFloor Mat

The mat is composed of a heating cable, a foil “radiator” to make a radiant surface, and a set of power leads for connection to the floor-sensing control. These mats are manufactured in sizes suitable to heat joist bays spaced 12″, 16″, and 19′.2″ on center.

Mats are rated either 120 VAC or 240 VAC. Select the mat length to fit into the joist space available. Multiple mats can be used to fill a larger area, however they must be wired together in parallel (not in series) if they are to be connected to the same control. NEVER combine 1 20-VAC mats with 240-VAC mats.

UnderFloor heat, GroupStat, LoudMouth, Heated floor mat, heat mat, radiant floor heat mat, radiant floor heating supply, radiant floor heating mat, radiant floor mat, flooring heating System, tile heating

Part 1: Designing a SunTouch UnderFloor System

In general, SunTouch UnderFloor should be installed in all floor areas where floor warming is desired. It can be installed to either warm the floor or to heat the space. If SunTouch is being installed to heat the space, first per form a heat loss calculation. Use RadiantWorks® or a similar program to calculate the heat loss of the room(s).

SunTouch can be expected to provide approximately 34 BTU/hr/sq.ft. of mat. This assumes the mats are installed per this manual, including the use of proper insulation techniques.

Make sure insulation is installed as shown on page 10. There must be a “dead air space” for UnderFloor mats to be effective This output also assumes a floor covering other than carpet and pad. The output will be greatly diminished with a carpet floor covering and/or the lack of proper insulation.

Determine how much Mat is needed for the Installation

To determine how much mat is needed, take one of two approaches:

1. For a rough estimate, multiply the wall-to-wall area by 75% – 80%. Convert this to linear feet of mat and select from the lengths of mat shown in the next pages.

2. For an accurate measurement, look under the subfloor to see where mats can be stapled. Looking carefully at each joist bay, measure the length of open area in that bay that can receive a mat, and select the mat from the table that fits the space.

Remember that these mats cannot be cut shorter to fit, nor modified in any way to fit multiple joist bays. Do not include in these measurements areas that contain items that would obstruct installation of the mat (return air ducts, supply ducts, light fixtures, etc.).

Where mats are not installed, the floor above wilt not gets very warm.

Wiring Multiple Mats Together

Each mat is designed to be installed in only one joist bay.

The mats cannot be cut shorter to fit a shorter joist bay or modified in any way to fill multiple Joist bays However; more than one mat may be installed in a Joist bay where there are barriers such as cross bracing. A typical installation is shown below.
Since several mats wilt be required to warm the floor area, the mats must be wired together in parallel (not in series) at a junction box below the floor, then electrical wire fed from there up to the floor-sensing control box. Select mats for the easiest wiring possible. If all the power leads end up at one end of the room, it will be much easier to wire them together in the junction box.

The junction box must be accessible after all finishing work is completed. Be sure to position the mats so that this is possible

Mat Voltage Requirements

SunStat controls are dual voltages 120/240 Volt.

Select either SunStat Pro programmable control or SunStat Non-Programmable control with either 120-VAC mats or 240-VAC mats. BUT NEVER mix 120-VAC mats with 240-VAC mats.

Observe these general voltage guide lines:

1. For areas totaling up to about 190 sq. ft. (about 15 amps), use 120-VAC mats with a 1 20-VAC SunStat

2. For areas exceeding about 190 sq. ft. and up to about 350 sq. ft., use 240-VAC mats with a any of SunStat to have mats totaling 14 amps or less.

3. Use 240-VAC mats with SunStat dual Voltage 240- VAC SunStat Relay control system for mats totaling more than 14 amps at 240VAC.
Regardless of the voltage requirements in a particular installation, make sure the circuit breaker can handle the load. Follow all electrical codes for determining the size of the breaker.

Floor-Sensing Controls

To control the SunTouch UnderFloor system, install either a programmable or non programmable control, floor-sensing SunTouch SunStat or SunStat with Relay system. The sensor should be installed per instructions.
Please reference the SunTouch catalog, or contact us at contact@flooringsupplyshop.com for more information.

These effective, UL-Listed mats deliver 10 watts/sq. ft. of floor area (about 34 BTU/hr/sq. ft.).

UnderFloor mats will warm wood, vinyl, laminates, or tile floor coverings.

With UnderFloor mats, most floors can be heated up to 12° to 15°F warmer than they would otherwise be.

Carpeted floors will not warm up as much as other floor coverings due to the high insulation value of carpet and padding. You may experience a temperature rise in the floor of only a 6° – 10°F, which may or may not meet your satisfaction. Insulation installed below the mats is essential to complete the installation.

Consider these benefits of UnderFloor mats:

1. Easy staple-up installation between floor joists.

2. Manufactured in nearly 40 different lengths in 12″, 16″, and 19.2″ widths. Mats of any size (same voltage) may be combined to heat any type of room.

3. 120-VAC and 240-VAC models for small to large projects.

4. Highest-quality heating wire using Aramid reinforcing, ETFE high-temperature insulation, and oxygen-free copper alloys for corrosion-resistance, temperature- resistance, abrasion-resistance, and longevity.

5. Shielded and fully grounded 10-ft. power lead for safety and jobsite durability (longer lengths available on request). Power leads are color-coded for 120 VAC and for 240 VAC.

Caution: Do not install UnderFloor mats in mortar or cement, or install them in the same control zone as SunTouch mats or WarmWire cables. These products have different heat output, and are manufactured for different applications.

Part 2: Electrical Service Rough-In

Circuit Over current Protection and GFCI Protection

The SunTouch mat must be protected by a ground fault circuit interrupter (GFCI). If the mats are directly powered through the SunStat Pro or SunStat controls, these already have an integral GFCI to protect the mats (do not install a GFCI type circuit breaker to supply a SunStat or SunStat Relay system, because the respective GFCIs may conflict and cause problems).

If a different type control or relay is used that does not have a built-in Class A GFCI, an indicating- type GFCI circuit breaker must be used to protect the mats.
This GFCI breaker serves as a local disconnect.

NOTE: Follow all local building and electrical codes.

It is recommended that the system be installed on its own dedicated circuit, directly from the circuit breaker panel.

However, small systems may be able to tap into an existing circuit. Consult an electrician.

Make sure there is adequate capacity for the mat(s) as well as any other items that may use this circuit.

The mat(s) should not be installed in a circuit with another GFCI (breaker or outlet), lighting circuit (low voltage, halogen, or other types that use ballasts or transformers that can interfere), or motor circuit (exhaust fan, hot tub, etc.) due to possible interference which can cause the

GFCI on the control to false-trip. The circuit breaker protecting the mat(s) must be no larger than 20 amps.

Load the circuit breaker with no more than the following: 12 amps on a 15-amp circuit breaker, 16 amps on a 20-amp circuit breaker.

Additional circuit breakers will be required for larger loads than these.

Select mats so that no more than 15 amps are run through a SunStat control

UnderFloor heat, GroupStat, LoudMouth, Heated floor mat, heat mat, radiant floor heat mat, radiant floor heating supply, radiant floor heating mat, radiant floor mat, flooring heating System, tile heating

120 Volt – UnderFloor Mat Sizes,Amperage Draw, and Resistance Ranges.- 12 O.C.
Mat Size
Amperage Draw
Resistance Range (ohms)
12″ x 5.5 ft.
0.4
247 – 302
12″ x 8 ft.
0.6
167 – 204
12″ x 10.5 ft..
0.9
121 – 148
12″ x 13 ft.
1.1
91 -119
12″ x 16 ft.
1.3
80 – 98
12″ x 19 ft.
1.5
67 – 82

UnderFloor heat, GroupStat, LoudMouth, Heated floor mat, heat mat, radiant floor heat mat, radiant floor heating supply, radiant floor heating mat, radiant floor mat, flooring heating System, tile heating

120 Volt – UnderFloor Mat Sizes,Amperage Draw, and Resistance Ranges.- 16 O.C.
Mat Size
Amperage Draw
Resistance Range (ohms
16″ x 4 ft.
0.4
258 – 315
16″ x 6 ft.
0.6
173 – 211
16″ x 8 ft..
0.8
126 – 154
16″ x 9.5 ft.
1.0
101 – 123
16″ x 12 ft.
1.3
82 – 101
16″ x 14 ft.
1.5
69 – 85
16″ x 16 ft
1.7
63 – 78
16″ x 18 ft.
1.9
53 – 65
16″ x 19.5 ft
2.1
45 – 56

UnderFloor heat, GroupStat, LoudMouth, Heated floor mat, heat mat, radiant floor heat mat, radiant floor heating supply, radiant floor heating mat, radiant floor mat, flooring heating System, tile heating

120 Volt – UnderFloor Mat Sizes, Amperage Draw, and Resistance Ranges.- 19.2 O.C.
Mat Size
Amperage Draw
Resistance Range (ohms
19.2″ x 4.5 ft.
0.7
170 – 207
19.2″ x 6.5 ft.
0.9
127 – 155
19.2″ x 8 ft..
1.0
103 – 126
19.2″ x 9.5 ft.
1.3
83 – 102
19.2″ x 11.5 ft.
1.5
71 – 87
19.2″ x 13 ft.
1.7
63 – 78
19.2″ x 14.5 ft..
1.8
54 – 66
19.2″ x 16 ft.
2.1
45 – 56

Large Systems on one Floor-sensing Control

For systems that are too large to directly power through one SunStat, but must be operated by one floor sensing control, use the SunStat with Relay control for best performance.

Contact a flooringsupplyshop.com or the factory for more information.

A contactor (relay) may also be used. Consult an electrician concerning the use of a contactor, and be sure to protect it with a GFCI breaker.

Install Electrical Boxes

SunStat box.

Decide on the location for the floor-sensing control. Usually this will be in the same room as the floor being warmed, but it can be mounted almost anywhere as long as it is not in a confined space where airflow is restricted. To reach this box with the mats, the mat power leads and the sensor wire leads can both be extended if needed with the appropriate size wire at a junction box.

The control electrical box may be a single-gang plastic deep box, but be sure to follow all electrical code requirements for box fill, grounding, etc. when determining the correct box for a particular application.

The control box should be located on interior walls, typically 60″ from the floor, according to code requirements.

NOTE: The SunStat sensor wire can be up to 50 ft. long, extended with 22- or 24-AWG wire.

UnderFloor heat, GroupStat, LoudMouth, Heated floor mat, heat mat, radiant floor heat mat, radiant floor heating supply, radiant floor heating mat, radiant floor mat, flooring heating System, tile heating

240 Volt – UnderFloor Mat Sizes,Amperage Draw, and Resistance Ranges.- 12 O.C.
Mat Size
Amperage Draw
Resistance Range (ohms
12″ x 10.5 ft..
0.4
500 – 611
12″ x 16 ft.
0.6
336 – 411

UnderFloor heat, GroupStat, LoudMouth, Heated floor mat, heat mat, radiant floor heat mat, radiant floor heating supply, radiant floor heating mat, radiant floor mat, flooring heating System, tile heating

240 Volt – UnderFloor Mat Sizes,Amperage Draw, and Resistance Ranges.- 16 O.C.
Mat Size
Amperage Draw
Resistance Range (ohms
16″ x 8 ft.
0.4
521 – 636
16″ x 12 ft.
0.6
362 – 443
16″ x 16 ft
0.8
253 – 310
16″ x 19.5 ft
1.0
207 – 253

UnderFloor heat, GroupStat, LoudMouth, Heated floor mat, heat mat, radiant floor heat mat, radiant floor heating supply, radiant floor heating mat, radiant floor mat, flooring heating System, tile heating

240 Volt – UnderFloor Mat Sizes, Amperage Draw, and Resistance Ranges.- 19.2 O.C.
Mat Size
Amperage Draw
Resistance Range (ohms
19.2″ x 6.5 ft.
0.4
526 – 643
19.2″ x 9.5 ft.
0.6
359 – 439
19.2″ x 13 ft..
0.9
256 – 313
19.2″ x 16 ft.
1.0
207 – 253
19.2″ x 19 ft.
1.3
167 – 204

Other junction boxes: It is highly recommended that a separate steel electrical junction box be mounted below the subfloor or in the wall in a location to which the mat power leads can be routed.

A separate wiring drop
can be made from the control box down to this junction box. This makes it much easier to install the system.

Bottom Plate Work

Drill a hole up through the wall bottom plate to route the power wiring from the control box to the mats below the floor.

Rough-in Wiring

Install electrical wiring from the power source breaker to the control electrical box, and then to the junction box below the floor for the mat leads.

Leave 6″–8″ of extra wire at the control box and junction box. Refer to the wiring diagrams in Part 6 for assistance.

UnderFloor heat, GroupStat, LoudMouth, Heated floor mat, heat mat, radiant floor heat mat, radiant floor heating supply, radiant floor heating mat, radiant floor mat, flooring heating System, tile heating

Diagram showing Method 1 for installing the floor sensor into the subfloor.

Install SunStat Sensor

A floor sensor comes with the SunStat control and must be installed correctly to control the floor temperature.

Remember to locate the sensor in a floor where a mat is located.

The following are recommended methods for installing the sensor. Other equivalent methods may be used.

Before installing the sensor, make sure to test it with an ohmmeter.

Method 1. Since a sensor may be difficult to install in some existing floors, the sensor may be placed under the subfloor.

However, keep in mind that the temperature the sensor gives will not be a true floor surface temperature and the floor-sensing control may need to be adjusted accordingly.

Drill a hole through the bottom plate of the wall to route the sensor wire.

Feed the sensor wire down from the control box through the floor. (A fish-tape may need to be used in order to do this.)

The most accurate method is to drill a 3/4″–1″-long hole at an angle into the bottom of the subfloor (drilling at an angle prevents puncturing through floor surface). Locate this hole in a joist bay directly over where a mat will be installed, about 2″ from the joist. Insert the sensor into the angled hole and seal it with adhesive. Insulate the sensor with additional “blueboard” or fiberglass insulation, 1″–2″ thick and 6″ square, adhered and sealed under the sensor. This will isolate the sensor from the heated joist space and give a truer floor surface temperature.

Method 2. If it is not possible to drill a hole to set the sensor in the subfloor, it may be held flat to the subfloor with a nylon wire clip.

Locate the sensor in a joist bay directly over where a mat will be installed, about 2″ from the joist. Insulate the sensor with additional “blueboard” or fiberglass insulation, 1″–2″ thick and 6″ square. This will help isolate the sensor from the heated joist space.

Method 3: Remove the grout 1/4″ to 1/2″ deep. Install sensor. Reinstall grout over the sensor and sensor wire.

UnderFloor heat, GroupStat, LoudMouth, Heated floor mat, heat mat, radiant floor heat mat, radiant floor heating supply, radiant floor heating mat, radiant floor mat, flooring heating System, tile heating

Method 3. If possible, install the sensor directly into or under the floor covering area.

If the floor surface is tiled, a grout line can be removed and the sensor laid into this grout line.

Drill a hole into the wall behind the baseboard trim area and directly below the control electrical box.

Feed the sensor through the knockout, down to the hole that was drilled near the floor, and out into the floor above where the heating mat will be installed.

Locate the sensor at least 1 ft. from outside walls and near the center of a joist space.

Complete the rest of the installation before covering or re grouting over the sensor.

Sample Kitchen Layout Using UnderFloor Mats

UnderFloor heat, GroupStat, LoudMouth, Heated floor mat, heat mat, radiant floor heat mat, radiant floor heating supply, radiant floor heating mat, radiant floor mat, flooring heating System, tile heating

Each UnderFloor mat is designed to be installed in only one joist bay. The mats cannot be cut shorter to fit a shorter joist bay or modified in any way to fill multiple joist bays.

However, more than one mat may be installed in a joist bay where there are barriers such as cross bracing or blocking.

In this kitchen layout, four 9.5′ × 16″ and eight 4′ × 16″ mats are required to warm the floor area.

The mats are wired together in parallel (not in series) at junction boxes below the floor, then electrical wire is fed over to the FloorStat control.

Select mats for the easiest wiring possible. If all the power leads end up at one end of the room, it will be much easier to wire them together in the junction boxes. Junction boxes must be accessible after all finishing work is completed.

Part 3: Install the UnderFloor Mat

Important – Read

Do not allow the foil radiator of the mat to be mounted such that it contacts metal objects such as

nails, staples, metal pipes, heating ducts, and joist straps. Keep the mat at least 2″ away

from recessed fixtures (lights, etc.), ventilation openings, and other openings.

Keep the mat at least 8″ away from the edges of outlet boxes and junction boxes used to mount surface lighting fixtures.

Keep the mat at least 2” away from recessed fixtures (lights, etc.), ventilation openings, and other openings.

Keep the mat at least 6″ away from heat-sensitive items such as toilet rings, flexible ducting, and other items rated less than 194°F (90°C). Consult manufacturers of those items.

REMEMBER:

Pay careful attention to areas where ductwork, wiring, or other items do not allow the mat to be installed. Keep in mind that where mats are not installed, the corresponding floor area above

will not get very warm.

Before installing the mat, inspect all joists as well as the underside of the subfloor for nails, screws, or other sharp objects that protrude into the joist cavity.

These items can damage the mat,and must be removed, cut off, or bent flat against the underside of the subfloor or the side of the joist(s).

Do not staple, cut, or damage the foiled heating portion of the mat in any way.

The fiber mesh of the mat is the portion that will be used to staple the mat to the joists cavity.

UnderFloor heat, GroupStat, LoudMouth, Heated floor mat, heat mat, radiant floor heat mat, radiant floor heating supply, radiant floor heating mat, radiant floor mat, flooring heating System, tile heating

1. Measure between the floor joists where mat(s) will be installed.

Measure the width of the mat selected to fit between these joists. The difference between these measurements determine how much mat mesh remains for stapling to each side of the joists.

Because the distance between floor joists can vary, taking these measurements will help ensure the mat will be centered between the joists. It is also prudent to test fit the mat by holding

the mat up into the joist cavity.

2. If the mat begins near the rim joist, measure about 6″ out from that rim joist.

This will allow enough room for the mat power leads, and will prevent unnecessary heating of the wall cavity above the floor.

3. Measure 2″ below the subfloor and mark the joists on both sides of the joist cavity.

UnderFloor heat, GroupStat, LoudMouth, Heated floor mat, heat mat, radiant floor heat mat, radiant floor heating supply, radiant floor heating mat, radiant floor mat, flooring heating System, tile heating

4. To help hold up the power leads while installing the mat, fasten one Nail Tite over the power leads

5. Hold the mat up along one joist and begin stapling the mat mesh along the 2″ mark from the subfloor. Staple every 4″ to 6″ for about 2 ft. to get started.

6. At the other end of the mat, place a nail into the joist at 2″ below the subfloor. Hang the fiber mesh of the mat onto the nail. This will make it much easier to staple the rest of the mat.

UnderFloor heat, GroupStat, LoudMouth, Heated floor mat, heat mat, radiant floor heat mat, radiant floor heating supply, radiant floor heating mat, radiant floor mat, flooring heating System, tile heating

7. Continue stapling the mat mesh at 2″ below the subfloor, every 4″ to 6″.

Then remove the nail at the end that held it up.

Power Lead Installation

If not already done so, mount a junction box below the subfloor within reach of the mat power leads.

Install more than one junction box, if needed, for larger jobs.

The junction box must remain accessible in accordance with electrical codes, so consider the location of the junction box carefully should the ceiling be finished after installation of the mat(s).

Route the power leads from the mat(s) to the junction box following all electrical and building codes using

Junction box with multiple sets of mat lead wires, connected in parallel, and connected to the

power supply. conduit and additional electrical boxes where required.

Junction box with multiple sets of mat lead wires, connected in parallel, and connected to the power supply.

UnderFloor heat, GroupStat, LoudMouth, Heated floor mat, heat mat, radiant floor heat mat, radiant floor heating supply, radiant floor heating mat, radiant floor mat, flooring heating System, tile heating

For multiple mats, follow all electrical codes concerning “box fill” maximums.

Connect the leads in parallel (black-to-black, white-to-white), and not in series.

Connect the mat leads to the power drop from the control electrical box or

SunStat sub control, or contactor.

Again, do not overload the control.

The SunStat and Relay control must not be loaded with over 15 amps of mats.

Part 4: Final Wiring

UnderFloor heat, GroupStat, LoudMouth, Heated floor mat, heat mat, radiant floor heat mat, radiant floor heating supply, radiant floor heating mat, radiant floor mat, flooring heating System, tile heating

The mat power leads and sensor wire connected to the control at the electrical box.

Install the Control

Install the control(s) for the mats according to the wiring diagrams provided with the controls.

(See Part 6 Wiring Diagram).

Connect the power supply leads, the power drop to the mat junction box, and the floor sensor wire to the SunStat. Follow proper wiring procedures.

It is a good idea to over wrap the wire nuts with electrical tape to further secure the wires into the wires nuts before pushing the control back into the electrical box.

Test the System

After the controls are installed and connected, energize the system briefly to test operation of all components.

Refer to the installation sheets provided with the SunStat for proper setting.

Without floor insulation, the mat will not heat the floor. When the SunStat calls for heat to the mat, the mat will begin to feel warm to the touch within 1 to 2 minutes or so. If this does not

occur, re check the SunStat settings, wiring connections, and power supply.

Apply the Warning Label

Apply the Radiant Heating Warning Label (included with this manual) to the control or nearby location.

Part 5: Install the Insulation

UnderFloor heat, GroupStat, LoudMouth, Heated floor mat, heat mat, radiant floor heat mat, radiant floor heating supply, radiant floor heating mat, radiant floor mat, flooring heating System, tile heating

REMEMBER: Proper insulating and sealing of the floor cavity is necessary for the performance of SunTouch UnderFloor mats.

Install R-13 to R-19 fiberglass insulation below the mat. Gently press the insulation up to the mat for best results and secure in place with rods, staples, or other method.

A gap between the insulation and mat is acceptable but will not give the best heating results.

Make sure to insulate at the end of all heated joist cavities. Install insulation vertically in these areas to seal the ends of the heated joist areas or, 6″ after the mat “stops” in a joist space, push the insulation up tight against the subfloor and staple to the subfloor.

This ensures that no heated air can escape from the heated joist space. If this is not done, much heat will “escape” horizontally through band joists, rim joists, exterior walls, and open ends of joist spaces, and the floor will not warm as it should.

Seal openings around pipes, waste lines, ducts, joist blocking, and all other gaps with silicone caulking or urethane foam.

Wiring Diagram

Typical Electric Wiring Diagram with FloorStat Control (120 V)
Dedicated 120-V, 20-amp
(maximum) circuit (must be GFCI protected unless a GFCI SunStat is
used)

UnderFloor heat, GroupStat, LoudMouth, Heated floor mat, heat mat, radiant floor heat mat, radiant floor heating supply, radiant floor heating mat, radiant floor mat, flooring heating System, tile heating

All electrical work must be done by a qualified licensed electrician in accordance with local building and electrical codes, and the National Electrical Code (NEC), especially Article 424, Part IX of the NEC, ANSI/NFPA70 and Section 62 of CEC Part 1.

Typical Electric Wiring Diagram with FloorStat Control (240 V)

Dedicated 240-V, 20-amp (maximum) circuit (must be GFCI protected unless a GFCI SunStat is used).

UnderFloor heat, GroupStat, LoudMouth, Heated floor mat, heat mat, radiant floor heat mat, radiant floor heating supply, radiant floor heating mat, radiant floor mat, flooring heating System, tile heating

All electrical work must be done by a qualified licensed electrician in accordance with local building and electrical codes, and

the National Electrical Code (NEC), especially Article 424, Part IX of the NEC, ANSI/NFPA70 and Section 62 of CEC Part 1.

Typical Electric Wiring Diagram with SunStat Control and Contactor(s) (240 V)

Dedicated 240-V. contactor circuit is GFCI Class A or B protected.

UnderFloor heat, GroupStat, LoudMouth, Heated floor mat, heat mat, radiant floor heat mat, radiant floor heating supply, radiant floor heating mat, radiant floor mat, flooring heating System, tile heating

All electrical work must be done by a qualified licensed electrician in accordance with local building and electrical codes, and

the National Electrical Code (NEC), especially Article 424, Part IX of the NEC, ANSI/NFPA70 and Section 62 of CEC Part 1.

How to Connect the LoudMouth Monitor to the Mat Power Leads

LoudMouth, Heated floor mat, heat mat, radiant floor heat mat, radiant floor heating supply, radiant floor heating mat, radiant floor mat, flooring heating System, tile heating, floor heat cable, radiant flooring, radiant floor heat system, floor warming system, heated floor system, under floor heat

Illustrations showing how to connect the LoudMouth monitor to two mats (left) ,and how to connect the LoudMouth to three mats (right). The LoudMouth can monitor no more than three mats simultaneously.

Do NOT leave the power leads connected in “series” like this when making final wiring connections; the mats will not heat sufficiently. When making final wiring connections, mats must be wired in parallel.

Part 7: Troubleshooting Guide

If problems arise with the SunTouch UnderFloor mat or its related electrical components, please consult this trouble shooting guide.
If not qualified to perform electrical work, it is highly recommended that a qualified, licensed electrician be hired.

Any electrical troubleshooting work should be performed with the power removed from the circuit, unless otherwise noted.
Although this troubleshooting guide is provided to assist with problems experienced with a SunTouch floor warming system, results are never guar anteed. SunTouch does not assume any liability or responsibility for dam age or injury that may occur from using this guide.

Problem
Possible Cause
Solution
Mat resistance measurement is outside the range printed on the nameplate label. An analog ohmmeter (using a moving needle) was used to take the reading. Obtain a digital ohmmeter able to read 0 to 20,000 ohms and re measure the resistance.
If measurement shows an open or short circuit, the heating wire has been damaged. Record resistance between all wires and contact the manufacturer.
If measurement is just a little low or high, room temperature has affected the resistance. Make the room temperature 75° – 85°F, or contact the manufacturer.
The resistance measurement could be from more than one mat wired in series, or wired in parallel. Either will provide false resistance readings. Make sure resistance measurements are for only one mat at a time. When connecting more than one mat to the control, multiple mats must be wired in parallel (i.e., black to black, white to white).
The ohmmeter may be set to the wrong scale. For instance, the 200 K ohms scale measures up to 200,000 ohms. The ohmmeter should typically be set to the 200 ohms scale, with the exception of mats having a rating above 200 ohms on their nameplate label. If the resistance reading is outside the range printed on the nameplate label, contact the manufacturer.
Floor is not getting warm. Mat has been damaged. Measure mat resistance. Check for both “open circuit” and “short circuit” as detailed earlier in this manual. If damaged, record resistances between all wires and contact the manufacturer.
GFCI has tripped, indicated by a light on the control. Light may be labeled “GFI”, may be below the words “Stand by”, or on the button labeled “Test”. Check for loose wire connections. Reset the GFCI on the control or circuit breaker. If it trips again, check for a short circuit in the mat as detailed earlier in this manual. If mat is damaged, record resistance between all wires and contact the manufacturer. If mat is not damaged, replace the GFCI control. Also see “GFCI conflicts” below.
Incorrect voltage supplied, or mismatched electrical components used. Measure “line” voltage, then measure “load” voltage. Both 120-V mats and controls have black and white leads. 240 V mats have black and blue leads, and 240-V controls have black and red leads.
Concrete slab floor. Surface temperatures rise slowly in a slab. If, after 5 to 8 hours of heating, the floor is not warmer to the touch, check for mat damage (see “Mat has been damaged” above). Measure “load” voltage/amperage to mat.
Floor heats continuously. Mats are wired in “series” or “daisy chained” (end-to-end). Multiple mats must be connected in “parallel” (or black-to black, white-to-white).
Sensor is loose or broken. If control has a digital display, it may indicate “LO”. SunTouch controls have a floor sensor. Pull the sensor wires loose from the control and reinsert them. If this does not solve the problem, measure resistance across the sensor wires. For a SunTouch control the resistance should be between 17,000 ohms (at 55°F) and 8,000 ohms (at 85°F). See sensor wire resistance values in this Manual
Incorrect wiring. The control was “bypassed” when it was wired to the power supply. Make sure wiring connections are correct. Consult the wiring diagram on the back of the control, the instructions that came with the control, or the wiring diagram in this manual.
Defective control. Return control to dealer for replacement.
Floor temperature shows “HI” or may show temperature over 100°F. Floor sensor is not wired properly, or is located incorrectly. Make sure only one floor sensor is connected to the control. Also see “Sensor is loose or broken” above.
Control is not working correctly. If a programmable control, the programming may be incorrect. Carefully read and follow control programming instructions.
Incorrect voltage supplied, or mismatched components used. Test voltage, verify parts. See “Incorrect voltage supplied” above.
Floor sensor is not wired properly, or is not working properly. Make sure only one floor sensor is connected to the control. Also see “Sensor is loose or broken” above.
Loose connection(s) on line side and/or load side of control. Remove and reinstall the wire nuts at each connection. Make sure the wire nuts are tight. Check all connections back to the breaker.
Defective control. Return control to dealer for replacement.
Control is not working at all. No power is supplied. Check circuit breaker. Measure voltage at the control. Check all connections between breaker and control.
Floor sensor is not wired properly, or is not working properly. Make sure only one floor sensor is connected to the control. Also see “Sensor is loose or broken” above.
Defective control. Return control to dealer for replacement.
GFCI conflicts and false-trips. More than one GFCI on the circuit. GFCI units will sometimes trip when there is nothing wrong with the equipment on the circuit, but when there is more than one GFCI. Reroute power to avoid having more than one GFCI on the circuit.
An electric motor or a ballasted light source is sharing the circuit with the mat. Electric motors and other electrical devices can cause a GFCI to false-trip. Run a dedicated circuit to the floor warming system.

www.suntouch.com

Click here for SunTouch VIDEO Library

SunTouch vs. Product A SunTouch vs. Product B

SunTouch Floor Heating Mat Links

SunTouch Mats Spec and installation SunTouch Mat SpecificationUnderfloor Spec and Installation

SunTouch Floor Heating Spool Links

SunTouch WarmWire Installation Guidelines SunTouch WarmWire StrapWarmWire Installation GuidelinesWarmWire Order Instruction and Information

Heating Controls Links

Programmable SunStat SpecOwner’s Manual Programmable 500670-SBOwner Manual Non Programmable 500675

SunStat Non Programmable Spec SunStat Relays ControlLoudMouth Operating Instruction

Misc SunTouch Links

SunTouch 25 year Limited Warranty EMF Electromagnetic fields Frequently Asked Questions Repair Heating Wire Suntouch Low Price Guarantee

The post Underfloor heating Specifications and installation procedure first appeared on Flooring Supply Shop Blog.

One thought on “Underfloor heating Specifications and installation procedure

  1. Someone essentially help to make critically articles I might state. This is the first time I frequented your website page and to this point? I amazed with the research you made to create this particular post extraordinary. Fantastic task!

Leave a Reply

Your email address will not be published. Required fields are marked *

Chat with us Chat